12 - 79
MELSEC-A
12 CONTROL AUXILIARY FUNCTIONS
(b) AFTER mode
The M code ON signal (XD, XE, XF) is turned ON at the positioning
completion, and the M code is stored in " Md.32 Valid M code".
01
00
*
m1
m2
V
t
OFF
ON
OFF
OFF
ON
ON
0
0
1
Positioning start signal
BUSY signal
M code ON signal
Positioning
* m1 and m2 indicate set M codes.
Md. 32 Valid M code
Da. 1 Operation pattern
*
Cd. 14 M code OFF request
[X4,X5,X6]
[Y10, Y11, Y12]
[XD,XE,XF]
Fig. 12.39 M code ON/OFF timing (AFTER mode)
(2) M code OFF request
When the M code ON signal (XD, XE, XF) is ON, it must be turned OFF by the
sequence program.
To turn OFF the M code ON signal, set "1" (turn OFF the M code signal) in
" Cd.14 M code OFF request".
Buffer memory address
Setting item
Setting
value
Setting details
Axis 1 Axis 2 Axis 3
Cd.14
M code OFF
request
1
Set "1: Turn OFF the M code ON signal".
1153
1203
1253
* Refer to section "5.7 List of control data" for details on the setting details.
The next positioning data will be processed as follows if the M code ON signal is
not turned OFF. (The processing differs according to the " Da.1 Operation
pattern".)
Da.1 Operation pattern
Processing
00
Independent positioning control
(Positioning complete)
01
Continuous positioning control
The next positioning data will not be executed until the M code ON
signal is turned OFF.
11
Continuous path control
The next positioning data will be executed, but a warning "M code
ON signal ON start" (warning code: 503) will occur.
Summary of Contents for A1SD75M1
Page 2: ......
Page 20: ...A 18 MEMO...
Page 22: ...MEMO...
Page 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Page 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Page 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Page 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Page 334: ...MEMO...
Page 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Page 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Page 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Page 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Page 745: ......