50
<Energy monitor settings>
1. General description
End user can monitor accumulated(
*
1
)
‘Consumed electrical energy’ and ‘Delivered heat energy’
in each operation mode(
*
2
) on the main remote controller.
*
1
Monthly and Year to date
*
2
- DHW operation
- Space heating
- Space cooling
Refer to the menu tree in “9-3. Main Settings Menu” for how to check the energy, and “6-19. DIP switch functions” for the details on DIP-SW setting.
Either one of the following 2 methods is used for monitoring.
Note: Method 1 should be used as a guide. If a certain accuracy is required, the 2nd method should be used.
(1) Calculation internally
Electricity consumption is calculated internally based on the energy consumption of outdoor unit, electric heater, water pump(s) and other auxiliaries.
*
3
Delivered heat is calculated internally by multiplying delta T (Flow and Return temp.) and flow rate measured by the factory fitted sensors.
Set the electric heater capacity and water pump(s) input according to indoor unit model and specs of additional pump(s) supplied locally. (Refer to the menu tree
in
“9-3. Main Settings Menu”)
Booster heater1
Booster heater2
Immersion
heater
*
1
Pump1
*
2
Pump2
Pump3
Default
2 kW
4 kW
0kW
***(factory fitted pump)
0kW
0kW
EHST20C-VM2C
2 kW
0kW
0kW
***
When additional pumps supplied locally are
connected as Pump2/3, change setting ac
-
cording to specs of the pumps.
EHST20C-VM6C
2 kW
4 kW
0kW
***
EHST20C-YM9C
3 kW
6 kW
0kW
***
EHST20C-TM9C
3 kW
6 kW
0kW
***
EHST20C-VM2EC
2 kW
0kW
0kW
***
EHST20C-VM6EC
2 kW
4 kW
0kW
***
EHST20C-YM9EC
3 kW
6 kW
0kW
***
EHST20C-MEC
0kW
0kW
0kW
***
EHST20D-VM2C
2 kW
0kW
0kW
***
EHST20D-MEC
0kW
0kW
0kW
***
EHST20D-MHC
0kW
0kW
3 kW
***
EHST20D-VM2EC
2 kW
0kW
0kW
***
EHST20D-YM9C
3 kW
6 kW
0kW
***
ERST20C-MEC
0kW
0kW
0kW
***
ERST20C-VM2C
2 kW
0kW
0kW
***
ERST20D-MEC
0kW
0kW
0kW
***
ERST20D-VM2C
2 kW
0kW
0kW
***
EHPT20X-VM2C
2 kW
0kW
0kW
***
EHPT20X-VM6C
2 kW
4 kW
0kW
***
EHPT20X-YM9C
3 kW
6 kW
0kW
***
EHPT20X-TM9C
3 kW
6 kW
0kW
***
EHPT20X-MHCW
0kW
0kW
3 kW
***
EHST20C-MHCW
0kW
0kW
3 kW
***
EHST20D-MHCW
0kW
0kW
3 kW
***
*
1
Change setting to 3 kW when connecting optional immersion heater "PAC-IH03V2-E".
*
2
"***" displayed in the energy monitor setting mode means the factory fitted pump is connected as Pump 1 so that the input is automatically calculated.
*
3
When the cylinder unit is connected with a PUHZ-FRP or PUMY models, electricity consumption is not calculated internally. To display the electricity consumption,
conduct the 2nd method.
When anti-freeze solution (propylene glycol) is used for primary water circuit, set the delivered energy adjustment if necessary.
For further detail of above, refer to the menu tree in “9-3. Main Settings Menu”.
(2) Actual measurement by external meter (locally supplied)
FTC has external input terminals for 2 ‘Electric energy meters’ and a ‘Heat meter’.
If two ‘Electric energy meters’ are connected, the 2 recorded values will be combined at the FTC and shown on the main remote controller.
(e.g. Meter 1 for H/P power line, Meter 2 for heater power line)
Refer to the [Signal inputs] in section
“6. WIRING DIAGRAM”
for more information on connectable electric energy meter and heat meter.
● Connectable electric energy meter and heat meter
▪
Pulse meter type
Voltage free contact for 12VDC detection by FTC (TBI.3 1, 3 and 5 pin have a positive voltage.)
▪
Pulse duration
Minimum ON time: 40 ms
Minimum OFF time: 100 ms
▪
Possible unit of pulse
0.1 pulse/kWh
1
pulse/kWh
10
pulse/kWh
100 pulse/kWh
1000 pulse/kWh
Those values can be set by the main remote controller. (Refer to the menu tree in "9-3. Main Settings Menu".)
OCH570C