Graphic Operation Terminal F940GOT
Sampling Mode 5
5-5
5.2.1
SAMPLE COND.
Set the timing at which sampling is performed. When the sampling condition set here is satis-
fied, a specified data register is accessed and its data is stored.
The sampling condition, trigger (DEVICE) or constant cycle (CYCLIC) can be selected.
•
Sampling by trigger
When X, Y, M, S, T or C becomes ON (OFF
à
ON)
or OFF (ON
à
OFF)
,
sampling is performed. (D, Z and V cannot be specified.)
•
Sampling in constant cycle
A cycle (time interval) can be set within the range of 1 second to 10 days, 23 hours, 59 min-
utes and 59 seconds. Sampling is performed at the specified time interval.
u
u
u
u
Basic operation
CYCLIC
SET
SAMPLE COND.
Paragraph 5.2
Select "SAMPLE
COND." on the
screen.
The SET CONDITION
screen is displayed.
DEVICE
Select "DEVICE".
The screen 1 is
displayed.
Select "CYCLIC".
The screen 2 is
displayed.
1) Sampling by trigger
2) Sampling in constant cycle
1)
2)
Display the
device input
keyboard.
Device symbol
Device No.
ENT
OFF -> ON
Execute
the input.
Change over
"OFF -> ON" and
"ON -> OFF".
Select a bit device among X, Y, M, S, T and C.
SET
Display the
ten-key pad.
0 to 9
Set date, hour, minute
and second. Set date,
hour, minute and second.
ENT
They are changed over alternately.
[ SET CONDITION ]
END
SAMPLE COND.
M 0
DEVICE
SET
OFF->ON
Screen 1
[ SET CONDITION ]
END
SAMPLE COND.
0d 0h 0m 0s
CYCLIC
SET
Screen 2
Summary of Contents for F940GOT-LWD-E
Page 1: ...OPERATION MANUAL F940GOT SWD E F940GOT LWD E...
Page 4: ...Graphic Operation Terminal F940GOT 2...
Page 6: ...Graphic Operation Terminal F940GOT 4...
Page 8: ...Graphic Operation Terminal F940GOT 6...
Page 14: ...Graphic Operation Terminal F940GOT Contents vi...
Page 104: ...Graphic Operation Terminal F940GOT Alarm Mode 6 6 12...
Page 148: ...Graphic Operation Terminal F940GOT Creation of Display Screens 9 9 30...
Page 228: ...Graphic Operation Terminal F940GOT Changeover of Display Screen FX PCS DU WIN E 11 11 18...