61
DETAILS OF INPUT AND
OUTPUT SIGNALS
7
RWw2
Link parameter
expansion setting/
Instruction code
Set the instruction code for execution of operation mode rewrite, Pr. read/write,
error reference, error clear, etc.
(Refer to page 68)
The corresponding instruction is
executed by switching on RYF after completion of register setting. RXF switches on
on completion of instruction execution.
When a value other than "0 (100)" is set in
Pr. 544 CC-Link expansion setting
, upper
eight bits are link parameter expansion setting.
Example) When reading
Pr. 300
, instruction code is 0300H.
RWw3
Write data
Set the data specified by the RWw2 instruction code. (When required)
Switch RYF on after setting the RWw2 and this register.
Set zero when the write code is not required.
RWw4
Monitor code 3
Set the monitor code to be monitored. By switching on the RYC signal after setting,
the specified monitored data is stored to RWr
. (
indicates a register number.
(RWr4 to 7))
RWw5
Monitor code 4
RWw6
Monitor code 5
RWw7
Monitor code 6
RWw8
Alarm definition No.
Set how many alarm definitions in past to be read. Back to eight alarm definitions in
past can be read. (lower 8bits is H00)
Upper: H00 (latest alarm) to H07 (eight alarms in past)/lower: H00
When H08 to HFF are set, alarm definition becomes an unfixed value.
Device No.
Signal
Description