68
DETAILS OF INPUT AND
OUTPUT SIGNALS
7.2.3 Instruction codes
(1) Instruction code definition
Set the instruction code using a remote resister (RWw)
(Refer to page 60.)
The definition read by the instruction code is stored in the remote resister (RWr).
(Refer to page 64.)
Item
Read /
Write
Code
Number
Description
Operation mode
Read
H007B
H0000: Network operation
H0001: External operation
H0002: PU operation
Write
H00FB
H0000: Network operation
H0001: External operation
H0002: PU operation (
Pr. 79
= "6")
Monitor
Output frequency
Read
H006F
H0000 to HFFFF:
Running frequency .....Increments 0.01Hz
Speed .........................Increments 1r/min (when
Pr.37
= 1 to 9998 or
Pr.144
= 2 to 10, 102 to 110)
Output current
Read
H0070
H0000 to HFFFF: Output current (hexadecimal)
Increments 0.01A (55K or less) / 0.1A (75K or more)
Output voltage
Read
H0071 H0000 to HFFFF: Output voltage (hexadecimal) Increments 0.1V
Special monitor
Read
H0072
H0000 to HFFFF: Check the data of the monitor selected by the
instruction code H00F3.
Special monitor
selection No.
Read
H0073
H01 to H3C: Monitor selection data
Refer to monitor code.
(Refer to page 73.)
Write
H00F3
*1
When "100" is set in
Pr. 52 DU/PU main display data selection
, frequency setting is monitored during a stop and
output frequency is monitored during running.
*2
When a value other than 9999 is set in
Pr.430
under position control (
Pr.800
= 3), pulse monitor is selected. (FR-
A700 series)
*3
The inverter type, 55K and 75K differ according to -NA and -EC versions.
(Refer to page 1.)