FX2NC Series Programmable Controllers
Outputs 6.
6-5
6.2
Relay output specification
Table 6.4 :
Switched voltages (resistive load)
≤
240V AC,
≤
30V DC
Rated current / N points (resistive load)
•
FX
2NC
:Main units and Extension blocks
2A/1point, 4A/1COM(8A/2COM)
(See sec, 3.13, 6.2.2)
•
FX
2N
,FX
0N
:Extension blocks
2A/1point, 8A/COM
Max. Inductive load
80VA See table 6.5
Max. lamp load (tungsten load)
100W (1.17A/85V AC, 0.4A/250V AC)
Minimum load
When supply voltage < 24V DC allow at least 5mA flow
Response time (approx.)
OFF
Æ
ON
10ms
ON
Æ
OFF
10ms
Circuit isolation
by relay
Operation indication
LED is lit when coil is energized
Summary of Contents for FX2NC DS Series
Page 18: ...FX2NC Series Programmable Controllers Contents xvi ...
Page 20: ...FX2NC Series Programmable Controllers Introduction 1 ...
Page 50: ...FX2NC Series Programmable Controllers Terminal layouts 2 ...
Page 56: ...FX2NC Series Programmable Controllers Installation notes 3 ...
Page 78: ...FX2NC Series Programmable Controllers Installation notes 3 3 22 MEMO ...
Page 80: ...FX2NC Series Programmable Controllers Power supply 4 ...
Page 88: ...FX2NC Series Programmable Controllers Inputs 5 ...
Page 98: ...FX2NC Series Programmable Controllers Outputs 6 ...
Page 110: ...FX2NC Series Programmable Controllers Outputs 6 6 12 MEMO ...
Page 112: ...FX2NC Series Programmable Controllers Diagnostics 7 ...