FX2NC Series Programmable Controllers
Introduction 1.
1-21
1.5.3
Rules
1) Add the input/output points of the extension blocks and special functions blocks to the input/
output points of the main unit. The total number of input and output points should be no
more than 256 points. However, the total number of input points should be 184 points or
less, and the total number of output points should also be 184 points or less.
2) The FX
2NC
series main unit supplies control power (5V DC) to the extension blocks and
special function blocks. For this reason, the total current consumption of all the blocks
connected to the main unit should not exceed the current capacity of the main unit.
3) Next to the FX
2NC
-CNV-IF, up to 4 blocks can be connected. To connect a special function
unit, such as the FX-10GM or FX
2N
-1RM-E-SET, refer to the instruction manual of the
corresponding special function block.
Calculation form for system configuration
Enter current consumption values and input/output points of the extension blocks and special
function blocks while referring to Sec. 1.5.2, and then calculate the total current value
r
and
total input and output points
s
through
v
. From the obtained values, judge whether the blocks
can be connected.
Summary of Contents for FX2NC DS Series
Page 18: ...FX2NC Series Programmable Controllers Contents xvi ...
Page 20: ...FX2NC Series Programmable Controllers Introduction 1 ...
Page 50: ...FX2NC Series Programmable Controllers Terminal layouts 2 ...
Page 56: ...FX2NC Series Programmable Controllers Installation notes 3 ...
Page 78: ...FX2NC Series Programmable Controllers Installation notes 3 3 22 MEMO ...
Page 80: ...FX2NC Series Programmable Controllers Power supply 4 ...
Page 88: ...FX2NC Series Programmable Controllers Inputs 5 ...
Page 98: ...FX2NC Series Programmable Controllers Outputs 6 ...
Page 110: ...FX2NC Series Programmable Controllers Outputs 6 6 12 MEMO ...
Page 112: ...FX2NC Series Programmable Controllers Diagnostics 7 ...