Appendix A: Related Devices
Appendix A-1 Related Device List
109
FX
3U
-CF-ADP User's Manual
A
Re
la
te
d
De
vic
e
s
B
V
e
rsi
on
Inform
ati
o
n
Appendix A: Related Devices
Appendix A-1 Related Device List
The tables below show special auxiliary relays and special data registers used in CF-ADP instructions
(FNC300 (FLCRT) to FNC305 (FLSTRD)).
1. Special auxiliary relays
R: Read only W: Write only R/W: Read or Write
*1.
Cleared when the PLC mode is changed from STOP to RUN.
*2.
When an instruction for the CF-ADP is driven while the system is updating the status of special data
registers, execution of the instruction for the CF-ADP may be delayed by several scans. If this delay is
regarded as a problem, use this flag to stop the updating of the status.
2. Special data registers
R: Read only W: Write only R/W: Read or Write
*1.
Cleared when the PLC mode is changed from STOP to RUN.
Device
Name
Description
R/W
ch1
ch2
M8029
Instruction execution complete
Turns ON when the execution of CF-ADP instructions is completed,
and remains ON for 1 scan.
R
M8329
Instruction execution abnormal end
Turns ON when the execution of CF-ADP instructions has ended
abnormally, and remains ON for 1 scan.
R
M8067
Operation error
Turns ON when an operation error occurs.
R
M8402 M8422 CF-ADP instruction executing
Remains ON while an instruction for the CF-ADP is being
executed.
R
M8404 M8424 CF-ADP unit ready
Remains ON when the CF-ADP is ready for receiving commands.
R
M8405 M8425 CF card mount status
ON : CompactFlash
TM
card mounted status
OFF : CompactFlash
TM
card unmounted status
R
M8410 M8430 CF-ADP status renewal stop
Stops communication executed by the system to update the status
of special data registers (D8406 and D8426).
*2
R/W
M8418 M8438 CF-ADP instruction error
*1
Turns ON when an error occurs in an instruction for the CF-ADP.
R/W
Device
Name
Description
R/W
ch1
ch2
D8067
Error code for operation error
Stores the error code when an operation error occurs.
R
D8402
D8403
D8422
D8423
Step number of executing CF-ADP
instruction
*1
Stores the step number of an instruction for the CF-ADP.
R
D8406
D8426 CF-ADP status
Stores the status information of the CF-ADP.
R
D8408
D8428 CF-ADP version
Stores the version of the CF-ADP.
R
D8414
D8415
D8434
D8435
Error step number of M8418, Error step
number of M8438
*1
Stores the step number of an instruction for the CF-ADP where an
error occurs.
R
D8417
D8437
Error code in detail for CF-ADP
instructions
*1
Stores error code details when an error occurs in an instruction for
the CF-ADP.
R
D8418
D8438 Error code for CF-ADP instructions
*1
Stores the error code when an error occurs in an instruction for the
CF-ADP.
R
D8419
D8439 Operation mode display
Stores the communication function status being executed.
R