7.3 Grounding
7 - 5
1
OV
E
R
VI
EW
2
SYSTE
M
CO
N
F
IG
UR
A
T
IO
N
3
S
P
E
CI
F
ICA
T
ION
S
4
P
A
R
T
NA
ME
AND
SETTING
S
5
EMC AND
LO
W
VO
LT
AG
E
DIRE
C
T
IVE
6
IN
ST
AL
L
A
TI
ON
7
WIRING
8
OP
TI
ON
(2) Shared grounding (Good)
* Ground the system at one end.
To prevent noise from entering the GOT, use a short and thick wire for grounding between the ground and the panel to ensure
lower ground resistance.
(3) Common grounding (Not allowed)
* Do not connect the ground cables of the power equipment and control equipment with a wire.
If the cables are connected, noise from the power equipment may influence the control equipment, causing malfunction.
Recommended terminal shape
Applicable solderless terminal
RAV1.25- 3, V2- S3.3, V2- N3A, FV2- N3A
GOT
CN1A CN1B
CN2 CN3
FG
LG
FG
FG
LG
Power equipment
(servo, etc.)
Connection cable
Panel
grounding
Use a short and thick cable as much as possible.
Panel
grounding
GOT
FG
LG
FG
FG
CN1B
CN1A
CN3
CN2
LG
Power equipment
(servo, etc.)
Connection cable
The power equipment and
control equipment are
connected with a wire.
Panel grounding
Panel grounding
6.2mm
or less
6.2mm
or less
Terminal
screw
Solderless
terminal
Terminal
screw
Solderless
terminal
When wiring one cable to
one terminal
When wiring two cables to
one terminal
3.2
3.2