10.1 GOT Restoration Sheet
(7) Power supply system
Current status
The power from the same system is
used for the GOT, I/O equipment
(such as relay), and power
equipment (such as servo amplifier).
Used
Not used
Measure for the
equipment for
which the power
from the same
system is used
Connecting an isolation transformer
as well as separating the wiring of
the GOT power from that of the
power of the I/O equipment and
power equipment reduces the
influence of noise.
Effective
Ineffective
Main power
PLC power
AC200V
I/O power
Main circuit power
I/O
equipment
Power
equipment
PLC
GOT
Main power
PLC power
Isolation transformer
AC200V
I/O power
Main circuit power
I/O
equipment
Power
equipment
PLC
GOT