6 - 10
6.4 Control Panel Inside Temperature and Mounting Angle
6.4 Control Panel Inside Temperature and Mounting
Angle
When mounting the GOT to a panel or similar, set the display section as shown below.
When the temperature inside the control panel is 40 to 55°C or less, the mounting angle should be in the range 60 to 105
degrees.
• The GOT will be deteriorated earlier if it is used at the mounting angle other than the above. Therefore, the
temperature inside the control panel should be within 40°C.
* When mounting a multimedia unit (GT16MMMR), MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13), or
CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5°C against the maximum
values described in general specifications.
6.5 Installation Procedure
The GOT mounting procedure is as follows.
For the panel cutting dimensions of each GOT, refer to the following.
1.
Before installing the GOT to the panel or others, connect the GOT and battery connectors.
For other than GT1665, GT1662
Open the battery cover.
For GT1655
Open the CF card cover.
For GT1665, GT1662
Remove the battery holder.
GOT
Display
section
Control panel,
etc.
105
60