5 - 13
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4 Precautions for Wiring/Connecting the EMC
Directive-Compliant Product
Wire and connect GOT1000 series equipments as instructed below. If the GOT1000 series equipments are configured in
a way different from the following instructions, the system may not comply with EMC directives.
5.4.1
Power and ground wires wiring method
(1) Power and ground wires wiring method
Connect the power wire and connection cable as shown in the illustration, and be sure to attach a ferrite core
(TDK Corporation type ZCAT3035-1330) within the range shown below.
Lead the power wire and ground wire as shown in 5.1.2 (2).
Make sure to ground the LG cable, FG cable, and functional ground cable.
(a) 100-240VAC GOT power section
(b) 24VDC GOT power section
• For other than GT1655
GOT power supply section
GOT power supply section
INPUT
100-240VAC
(LG)
(FG)
90mm or less
Ferrite core
(ZCAT3035-1330)
INPUT
24VDC
+
-
90mm or less
Ferrite core
(ZCAT3035-1330)
(LG)
(FG)