(e) Total 24VDC average power consumption of the output module
W
24V
= 0 (W)
(f) Average power consumption due to voltage drop in the output section of the
output module
W
OUT
= 0 (W)
(g) Average power consumption of the input section of the input module
W
IN
= 0.004 24 2 1 = 0.192 (W)
(h) Power consumption of the intelligent function module
W
S
= 0 (W)
(i) Power consumption of overall system.
W = 0.95 + 3.8 + 0 + 0 + 0.192 + 0 = 4.942 (W)