7 - 9 7 - 9
7 I/O MODULES
MELSEC-ST
7.2.4 ST1Y2-TPE3 transistor output module (source type)
Transistor Output Module (source type)
Type
Specifications
ST1Y2-TPE3 Appearance
Number of occupied slice
modules
1
Number of occupied I/O points
CC-Link: 0 point for input, 2 points for output
PROFIBUS-DP: 2 points for each of input and output
Number of output points
2 points
Isolation method
Photocoupler
Rated load voltage
24VDC (+20/-15%, ripple ration within 5%)
Maximum load current
1.0A/point, 2.0A/common
Maximum inrush current
2.0A, 10ms or less
Leakage current at OFF
0.3mA or less
Maximum voltage drop at ON
0.15VDC (TYP.) 1.0A, 0.2VDC (MAX.) 1.0A
OFF to ON
0.5ms or less
Response time
ON to OFF
1.5ms or less (rated load, resistive load)
Surge suppressor
Zener diode
Protection function
• Yes (thermal protection, short circuit protection)
• Indicated by LED (When protective function is activated,
ERR. LED turns on and signal is output to head module)
• Automatic recovery
Wiring method for common
2 points/common
Dielectric withstand voltage
500VAC for 1 minute across DC external terminals and FG
Insulation resistance
10M or larger by insulation resistance tester across DC external
terminals and FG
By noise simulator of 500Vp-p noise voltage, 1
s noise width
and 25 to 60Hz noise frequency
Noise durability
First transient noise IEC61000-4-4: 1kV (bundle)
Protection of degree
IP20
Operating status
ON indication (LED)
Spring clamp type
ST1B-S3Y2 2-wire type + shield
Available base module
Screw clamp type
ST1B-E3X2 2-wire type + shield
Available coding element
ST1A-CKY-08 (orange) (factory-fit) Refer to Chapter 8 for details.
5VDC internal current
consumption
0.095A (TYP. all points ON)
(0.10A is shown on the rating plate of the module.)
Weight 0.03kg
11
21
ST1Y2
-TPE3
RUN
ERR.
External Connections
Terminal Layout
Terminal Block
No.
Signal Name
11 Y0
12 24G
13 Shield
21 Y1
22 24G
23 Shield
11
Y0
12
24G
13
21
Shield
22
Y1
23
24G
Shield
24G
+24V
Base Module
Output Module
L
L
2-wire
external load
Constant
Voltage
Circuit
2
3
3
1
Protection
circuit
Protection
circuit
2: Shield is grounded via the base module for the power distribution module.
3: Connection from power distribution module.
1: This FG terminal is not connected.
(Grounded at the FG contact of the base module for power distribution module.)
11
21
12
22
13
23
Module front
view
Summary of Contents for MELESEC-ST
Page 1: ......
Page 2: ......
Page 23: ...A 21 A 21 MEMO...
Page 114: ...10 22 10 22 10 MOUNTING AND INSTALLATION MELSEC ST MEMO...
Page 125: ...11 11 11 11 11 EMC AND LOW VOLTAGE DIRECTIVE MELSEC ST MEMO...
Page 163: ...Index 2 Index 2 MEMO Ind...
Page 165: ......
Page 166: ......