9 - 5 9 - 5
9 FUNCTIONS AVAILABLE BY USE OF SOFTWARE
MELSEC-ST
9.2.2 Functions Available by Use of GX Configurator-ST
Operation
method
Function Description
1) 2) 3)
Reference
section
Information monitor function
Monitors various information of the head module and slice
modules.
1
Status monitor function
Monitors the operating status of the slice modules and the error
history, etc. of the head module.
2
Online module change
function
Replaces an I/O module or intelligent function module while
external power supply is on.
Note that the power distribution modules cannot be replaced.
2
Forced output test function
Forcibly outputs the Bw.n Bit Output, Ew.n Error Clear and
Ww.n Word Output of the head module and slice modules.
1
Input response time setting
monitoring function
Monitors the response time setting (0.5ms/1.5ms) of the input
module.
This
section (1)
Setting monitoring of output
status (CLEAR/HOLD) at
module error
Monitors the output status (CLEAR/HOLD) of the output
module.
CLEAR: Output is forcibly turned off when a module
becomes faulty.
HOLD: Output is held in the status as when a module
becomes faulty.
This
section (2)
Power supply capacity check
function
Judges whether the 5VDC maximum rated output current of the
power distribution module is sufficient for the total 5VDC internal
current consumption of the slice modules.
1
: Applicable, : N/A
1) Operate with GXConfigurator-ST.
2) Execute a command from the master station to perform operation.
3) Use the button or switch of the head module to perform operation.
1: For the operation of GX Configurator-ST, refer to the GX Configurator-ST Operating Manual.
2: For details, refer to the MELSEC-ST PROFIBUS-DP Head Module User's Manual.
Summary of Contents for MELESEC-ST
Page 1: ......
Page 2: ......
Page 23: ...A 21 A 21 MEMO...
Page 114: ...10 22 10 22 10 MOUNTING AND INSTALLATION MELSEC ST MEMO...
Page 125: ...11 11 11 11 11 EMC AND LOW VOLTAGE DIRECTIVE MELSEC ST MEMO...
Page 163: ...Index 2 Index 2 MEMO Ind...
Page 165: ......
Page 166: ......