5.3 Output Instructions
5.3.3 Counter
OUT_C
5.3.3
Counter
OUT_C
F
unct
i
on
(1) When the operation results up to the OUT_C instruction change from OFF to ON, 1 is added
to the current value (count value) and the count up status (current value = set value), and
the contacts respond as follows:
(2) No count is performed with the operation results at ON. (There is no need to perform pulse
conversion on count input.)
(3) After the count up status is reached, there is no change in the count value or the contacts
until the RST instruction is executed.
(4) A negative number ( 32768 to 1) cannot be set as the setting value for the timer.
If the set value is 0, the processing is identical to that which takes place for 1.
OUT_C
indicates the following instruction.
OUT_C
Input argument,
EN:
Executing condition
:Bit
CCoil:
Counter number
:Bit
CValue:
Counter set value
:ANY16
Output argument,
ENO:
Execution result
:Bit
Setting
data
Internal device
R ,ZR
J
\
U
\G
Zn
Constant
K
Others
Bit
Word
Bit
Word
CCoil
(CC only)
−
−
−
−
−
−
−
CValue
−
(Other than T
or C)
−
−
−
Normally open contact
Conduction
Normally closed contact
Non-conduction
U
n
i
versa
l
UD
Hi
g
h
Per
f
ormance
Structured ladder
ST
O
U
T_C
EN
ENO
CCoil
CValue
O
U
T_C
(EN, CCoil, CValue);
ENO:=
Summary of Contents for MELSEC Q Series
Page 1: ...Structured Programming Manual Mitsubishi Programmable Controller QCPU Common Instructions ...
Page 2: ......
Page 14: ...A 12 MEMO ...
Page 340: ...6 178 MEMO MTR ...
Page 708: ...7 368 MEMO ...
Page 776: ...8 68 MEMO ...
Page 796: ...9 20 MEMO ...
Page 804: ...App 8 MEMO ...
Page 812: ...Index 8 MEMO ...
Page 815: ......