Appendix 2 Correspondence between Devices and Addresses
App-7
A
APP
E
NDIX
Table App. 2-2 Correspondence between devices and addresses
Device
Expressing method
Example of correspondence between
device and address
Device
Address
Device
Address
Step relay
S
Sn
%MX2.n
S127
%MX2.127
SFC transition device
TR
TRn
%MX18.n
TR3
%MX18.3
SFC block device
BL
BLn
%MX17.n
BL3
%MX17.3
Link input
J
Jx\Xn
%IX16.x.n
J1\X1FFF
%IX16.1.8191
Link output
Jx\Yn
%QX16.x.n
J1\Y1FFF
%QX16.1.8191
Link relay
Jx\Bn
%MX16.x.1.n
J2\B3FFF
%MX16.2.1.16383
Link register
Jx\Wn
%MW16.x.1.n
%MD16.x.1.n
J2\W3FFF
%MW16.2.1.16383
%MD16.2.1.16383
Link special relay
Jx\SBn
%MX16.x.11.n
J2\SB1FF
%MX16.2.11.511
Link special register
Jx\SWn
%MW16.x.11.n
%MD16.x.11.n
J2\SW1FF
%MW16.2.11.511
File register
ZR
ZRn
%MW12.n
%MD12.n
ZR32767
%MW12.32767
%MD12.32767