11. OPTIONS AND AUXILIARY EQUIPMENT
11 - 63
Dimensions [mm]
Servo amplifier
Power factor
improving DC
reactor
Dimensions
W W1 H
D
(Note 1)
D1 D2 D3
d
Terminal
size
Mass
[kg]
Wire [mm
2
]
(Note 2)
MR-J4-10A(-RJ)
MR-J4-20A(-RJ)
FR-HEL-0.4K 70
60
71
61
21
M4
M4
0.4
MR-J4-40A(-RJ) FR-HEL-0.75K
85 74 81 61
21
M4 M4 0.5
MR-J4-60A(-RJ)
MR-J4-70A(-RJ)
FR-HEL-1.5K 85
74
81
70
30
M4
M4
0.8
MR-J4-100A(-RJ) FR-HEL-2.2K
Fig. 11.1
85 74 81 70
30
M4 M4 0.9
MR-J4-200A(-RJ) FR-HEL-3.7K
77 55 92 82 66 57 37 M4 M4 1.5
2 (AWG 14)
MR-J4-350A(-RJ) FR-HEL-7.5K
86 60 113 98 81 72 43 M4 M5 2.5 3.5
(AWG
12)
MR-J4-500A(-RJ) FR-HEL-11K
105 64 133 112 92 79 47 M6 M6
3.3 5.5
(AWG
10)
MR-J4-700A(-RJ) FR-HEL-15K
105 64 133 115 97 84 48.5 M6 M6
4.1 8
(AWG
8)
MR-J4-11KA(-RJ) FR-HEL-15K
105 64 133 115 97 84 48.5 M6 M6
4.1 14
(AWG
6)
MR-J4-15KA(-RJ) FR-HEL-22K
Fig. 11.2
105 64 93 175 117 104
115
(Note 1)
M6
M10
5.6
22 (AWG 4)
MR-J4-22KA(-RJ) FR-HEL-30K Fig.
11.3
114 72 100 200 125 101
135
(Note 1)
M6
M10
7.8
38 (AWG 2)
Note 1. Maximum dimensions. The dimension varies depending on the input/output lines.
2. Selection conditions of wire size is as follows.
Wire type: 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Construction condition: Single wire set in midair
Summary of Contents for MR-J4-100A
Page 9: ...A 8 MEMO ...
Page 61: ...1 FUNCTIONS AND CONFIGURATION 1 44 MEMO ...
Page 67: ...2 INSTALLATION 2 6 MEMO ...
Page 137: ...3 SIGNALS AND WIRING 3 70 MEMO ...
Page 261: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 291: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 30 MEMO ...
Page 299: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 319: ...9 OUTLINE DRAWINGS 9 20 MEMO ...
Page 461: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 36 MEMO ...
Page 511: ...14 COMMUNICATION FUNCTION 14 38 MEMO ...
Page 559: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 583: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 621: ...APPENDIX App 38 ...
Page 639: ......