12. ABSOLUTE POSITION DETECTION SYSTEM
12 - 35
(d) At the time of forced stop reset
210 ms after the forced stop is deactivated, the base circuit turns on, and RD turns on further 5 ms
after that, turns on. Always get the current position data using RD as the trigger before the position
command is issued.
1) When power is switched on in a forced stop status
OFF
210 ms
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
5 ms
During this period, get absolute position data.
Current position change
Power
supply
Base circuit
Pulse train command
Current position
Absolute position
data receive
Absolute position data
command transmission
SON
EM2
RD
Absolute position
data
2) When a forced stop is activated during servo on
95 ms
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5 ms
Pulse train command
Current position
Absolute position
data receive
Absolute position data
command transmission
Current position change
During this period, get absolute position data.
Base circuit
SON
EM2
RD
Absolute position
data
Summary of Contents for MR-J4-100A
Page 9: ...A 8 MEMO ...
Page 61: ...1 FUNCTIONS AND CONFIGURATION 1 44 MEMO ...
Page 67: ...2 INSTALLATION 2 6 MEMO ...
Page 137: ...3 SIGNALS AND WIRING 3 70 MEMO ...
Page 261: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 291: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 30 MEMO ...
Page 299: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 319: ...9 OUTLINE DRAWINGS 9 20 MEMO ...
Page 461: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 36 MEMO ...
Page 511: ...14 COMMUNICATION FUNCTION 14 38 MEMO ...
Page 559: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 583: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 621: ...APPENDIX App 38 ...
Page 639: ......