App. 5.8.3 Wiring CN9 and CN10 connectors
Handle with the tool with care when connecting wires.
(1) Wire strip
(a) Use wires with size of AWG 24 to 20 (0.22 mm
2
to 0.5 mm
2
) (recommended electric wire: UL1007)
and strip the wires to make the stripped length 7.0 mm ± 0.3 mm. Confirm the stripped length with
gauge, etc. before using the wires.
(b) If the stripped wires are bent, feazed or too thick due to twisting too much, fix the wires by twisting
lightly, etc. Then, confirm the stripped length before using the wires. Do not use excessively
deformed wires.
(c) Smooth out the wire surface and stripped insulator surface.
(2) Connecting wires
Before connecting wires, be sure to pull out the receptacle assembly from the header connector. If wires
are connected with inserted connector, the connector and the printed board may malfunction.
(a) Using extraction tool (1891348-1 or 2040798-1)
1) Dimensions and mass
[Unit: mm]
Mass : Approx. 20 g
Summary of Contents for MR-J4-100A
Page 9: ...A 8 MEMO ...
Page 61: ...1 FUNCTIONS AND CONFIGURATION 1 44 MEMO ...
Page 67: ...2 INSTALLATION 2 6 MEMO ...
Page 137: ...3 SIGNALS AND WIRING 3 70 MEMO ...
Page 261: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 291: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 30 MEMO ...
Page 299: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 319: ...9 OUTLINE DRAWINGS 9 20 MEMO ...
Page 461: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 36 MEMO ...
Page 511: ...14 COMMUNICATION FUNCTION 14 38 MEMO ...
Page 559: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 583: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 621: ...APPENDIX App 38 ...
Page 639: ......