30
Type
Low-inst
Standard
Mag-Only
(Inst trip only)
Generator
690V
500V
440V
400V
230V
Frame (A)
Rated insulation voltage Ui (V) AC
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
800A
Rated current
I
n (A)
AC Breaking
capacity (kA rms)
I
EC60947-2
I
cu/
I
cs
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
NF800-HEP
400 ~ 800
adjustable
3
4
Electronic trip relay
Adjustable ampere rating
Adjustable long time delay
operating time, short time delay
pick up and instantaneous
Short time delay pick up current
Variation is within
±
15% of
setting current
2 to 10
I
r
400
800-1000-1200-1400-
1600-2000-2400-2800-
3200-4000
450
900-1150-1350-1575-
1800-2250-2700-3150-
3600-4500
500
1000-1250-1500-1750-
2000-2500-3000-3500-
4000-5000
600
1200-1500-1800-2100-
2400-3000-3600-4200-
4800-6000
700
1400-1750-2100-2450-
2800-3500-4200-4900-
5600-6300
800
1260-1575-1890-2205-
2520-3150-3780-4410-
5040-6300
Instantaneous pick up current
Variation is within
±
15% of
setting current
4
I
n ~ 12
I
n
3200 ~ 9600
690
15/15
50/50
65/65
70/70
100/100
NF800-SEP
400 ~ 800
adjustable
3
4
Electronic trip relay
Adjustable ampere rating
Adjustable long time delay
operating time, short time delay
pick up and instantaneous
Short time delay pick up current
Variation is within
±
15% of
setting current
2 to 10
I
r
400
800-1000-1200-1400-
1600-2000-2400-2800-
3200-4000
450
900-1150-1350-1575-
1800-2250-2700-3150-
3600-4500
500
1000-1250-1500-1750-
2000-2500-3000-3500-
4000-5000
600
1200-1500-1800-2100-
2400-3000-3600-4200-
4800-6000
700
1400-1750-2100-2450-
2800-3500-4200-4900-
5600-6300
800
1260-1575-1890-2205-
2520-3150-3780-4410-
5040-6300
Instantaneous pick up current
Variation is within
±
15% of
setting current
4
I
n ~ 12
I
n
3200 ~ 9600
690
10/10
30/30
42/42
45/45
85/85
NF800-CEP
400 ~ 800
adjustable
3
Electronic trip relay
Adjustable ampere rating
Adjustable long time delay
operating time, short time delay
pick up and instantaneous
Short time delay pick up current
Variation is within
±
15% of
setting current
2 to 10
I
r
400
800-1000-1200-1400-
1600-2000-2400-2800-
3200-4000
450
900-1150-1350-1575-
1800-2250-2700-3150-
3600-4500
500
1000-1250-1500-1750-
2000-2500-3000-3500-
4000-5000
600
1200-1500-1800-2100-
2400-3000-3600-4200-
4800-6000
700
1400-1750-2100-2450-
2800-3500-4200-4900-
5600-6300
800
1260-1575-1890-2205-
2520-3150-3780-4410-
5040-6300
Instantaneous pick up current
Variation is within
±
15% of
setting current
4
I
n ~ 12
I
n
3200 ~ 9600
600
–
18/9
36/18
36/18
50/25
Electronic trip relay
Adjustable ampere rating,
instantaneous pick up current
3
4
Instantaneous pick up current
Variation is within
±
15% of
setting current
2 to 10
I
r