41
6.3 Selective-Interruption (Discrimination)
6.3.1 Selective-Interruption Combination
Following tables show combinations of main-circuit
selective coordination breakers and branch breakers
and the available selective tripping current at the set-
ting points at the branch-circuits.
Short-circuit point
Continuous supply
Healthy circuit
Main breaker
Branch breaker
Selection Conditions
1. The main breaker rated current, STD operating time
and INST pickup current are to be set to the maxi-
mum values.
2. When selecting the over-current range, also check
the conformity using the other characteristic curves.
Main breaker
STD pick up current.
Set up STD operating time in the
maximum value.
Set up inst pick up current
in the maximum value.
Branch
breaker
Icu : Rated breaking capacity
Note1 : Reted currents of main breakers are maximum values.
Note2 : Reted currents of branch breakers are 50A or less.
Main Breaker
Note 1
Branch
Breaker
BH-D6
TYPE C
BH-D6
TYPE B
NF100-SEP
NF250-SEP
Icu(kA)
50
50
6
6
1.6 Note2
1.6 Note2
1.6 Note2
3.5
3.5
Selective interruption combinations (MCB-MCCB)