43
Selective interruption combinations
440VAC (Sym. kA)
Icu : Rated breaking capacity
Note : Reted currents main breakers are maximum values.
NF100-SEP
NF100-HEP
NF250-SEP
NF250-HEP
NF400-SEP
NF400-HEP
NF630-SEP
NF630-HEP
NF800-CEP
NF800-SEP
NF800-HEP
NF1000-SS
NF1200-SS
NF1600-SS
Main Breaker
Branch
Breaker
NF30-SP
NF50-HRP
NF160-SP
NF160-SP T/A
NF250-SP
NF250-SEP
NF250-SP T/A
NF250-HP
NF250-HEP
NF250-HP T/A
NF400-SP
NF630-HEP
NF400-SEP
NF400-HEP
NF250-CP
NF250-CP T/A
NF400-CP
NF630-CP
NF100-RP
NF100-UP
NF225-RP
NF225-UP
NF400-UEP
NF630-UEP
NF800-UEP
NF630-SP
NF630-SEP
NF50-CP
NF60-CP
NF100-CP
NE100-CP T/A
NF160-HP
NF160-HP T/A
NF100-SP
NF100-SP T/A
NF100-SEP
NF100-HP
NF100-HP T/A
NF100-HEP
NF50-HP
NF60-HP
Icu(kA)
25
50
25
50
42
65
42
65
36
42
65
85
2.5
1.6
1.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
10
1.6
1.6
3.5
3.5
7.5
7.5
10
10
10
10
10
10
30
–
–
3.5
3.5
7.5
7.5
15
15
15
18
18
30
25
–
–
3.5
3.5
5
5
10
10
10
10
10
22
50
–
–
3.5
3.5
7.5
7.5
18
18
18
18
18
50
25
–
–
–
–
6.4
6.4
10
10
10
10
10
22
25
–
–
–
–
–
–
10
10
10
10
10
22
25
–
–
–
–
6.4
6.4
10
10
10
10
10
22
25
–
–
–
–
6.4
6.4
10
10
10
10
10
22
50
–
–
–
–
6.4
6.4
10
10
10
10
10
22
50
–
–
–
–
–
–
10
10
10
10
10
22
50
–
–
–
–
6.4
6.4
10
10
10
10
10
22
50
–
–
–
–
6.4
6.4
10
10
10
10
10
22
42
–
–
–
–
–
–
–
–
10
10
10
20
42
–
–
–
–
–
–
9.5
9.5
10
10
10
20
65
–
–
–
–
–
–
9.5
9.5
10
10
10
20
42
–
–
–
–
–
–
–
–
–
–
–
20
65
–
–
–
–
–
–
–
–
–
–
–
20
2.5
1.6
1.6
3.5
3.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
10
–
–
3.5
3.5
5
5
10
10
10
10
10
10
15
–
–
–
–
–
–
7.5
7.5
7.5
7.5
7.5
15
15
–
–
–
–
6.4
6.4
7.5
7.5
7.5
7.5
7.5
15
25
–
–
–
–
–
–
–
–
10
10
10
20
36
–
–
–
–
–
–
–
–
–
–
–
20
125
–
–
3.5
3.5
15
15
30
30
30
42
50
85
200
–
–
3.5
3.5
15
15
30
30
30
42
50
85
125
–
–
–
–
–
–
15
15
15
25
25
85
200
–
–
–
–
–
–
15
15
15
25
25
85
200
–
–
–
–
–
–
9.5
9.5
15
15
15
25
200
–
–
–
–
–
–
–
–
–
–
–
20
200
–
–
–
–
–
–
–
–
–
–
–
–
S
C
U