(8) Local remote controller operation prohibit setting
[Collective Setting/Monitor Screen]
1. Operations with all local remote controllers controlled with this controller can be prohibited.
[Group Setting/Monitor Screen]
1. Operations with the local remote controller for the selected group can be prohibited.
When this controller's SW3-5 operation prohibit range setting changeover has been set
to "ON (including system controller)", operations of the other system controllers can be
prohibited.
Setting method: Set on the [Collective Setting/Monitor Screen] or [Group Setting/Monitor Screen].
1. When the PROHIBIT switch is pressed, [ PROHIBIT , ON/OFF, MODE, TEMP., FILTER ]
will appear. Items that have already been prohibited will turn ON, and the permitted items will
flicker. All items will flicker on the [Collective Setting/Monitor Screen].
If the group is controlling LOSSNAY, [MODE, TEMP. ] will not appear.
2. Set the items to be prohibited or permitted with local remote controller operations.
• To prohibit or permit ON/OFF operations
:
Press the ON/OFF switch. The ON/OFF display will change when pressed.
• To prohibit or permit operation mode changeover
:
Press the MODE switch. The "MODE" display will change when pressed.
• To prohibit or permit room temperature adjustment
:
Press the TEMP.
or
switch.
The "TEMP" display will change when pressed.
• To prohibit or permit filter resetting operations
:
Press the FILTER switch. The "FILTER" display will change when pressed.
[Changes in display of each item] Flicker (Not set)
→
ON (Prohibit)
→
OFF (Permit)
When each item's switch is pressed, the related display will change as shown above from the
current display state.
[Meaning of displays]
3. The prohibited or permitted item will be set when the PROHIBIT switch is pressed, and local
remote controller operation of the items that are ON will be prohibited. The operation will be
permitted if the item is OFF or flickering (not set).
(*1) On the [Collective Setting/Monitor Screen], if all four items are flickering in step 3 above (nothing is
being operated), it does not mean that all operations are permitted. Instead this means that the previous set-
tings will be applied.
1. This function can be set only when this controller's SW-4 operation prohibit setting
changeover is set to "ON (Permit)". Settings cannot be made when set to prohibited.
If the function is used when the setting is prohibited, [- CENTRALIZED -], PROHIBIT ,
ON/OFF, MODE, TEMP., FILTER] will flicker.
2. The operation mode changeover and room temperature adjustment operations can-
not be prohibited for LOSSNAY groups.
11
GB
Display
ON
OFF or flickering (*1)
ON/OFF Local remote controller ON/OFF operation prohibited
Local remote controller ON/OFF operation permitted
MODE
Local remote controller operation mode changeover prohibited
Local remote controller operation mode changeover permitted
TEMP.
Local remote controller room temperature adjustment prohibited
Local remote controller room temperature adjustment permitted
FILTER
Local remote controller filter resetting prohibited
Local remote controller filter resetting permitted
Summary of Contents for PAC-SF44SRA
Page 35: ...35 GB ...
Page 69: ...69 D ...
Page 103: ...103 F ...
Page 137: ...137 E ...
Page 171: ...171 I ...
Page 205: ...205 NL ...
Page 206: ...HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WT03804X01 ...