8 . Installation settings and test run
Select the date with ▲ ▼
buttons, and tap the Set
button.
The selected screen is
displayed.
The selected screen is
displayed.
This can be operated while
cooling is stopped. When the
room temperature is too low
to start the cooling test run,
it operates for 30 minutes by
decreasing the set temperature
to 5°C.
Drain pump can be operated
independently.
⑧
Cooling test run
Cooling test run
Back
Start
When tapping [Start], test run starts
for 30 min. at 5°C in cooling.
Finish-condition of test run is follows.
Passage of 30 min./Stop the IU/Change "Set temp",
"Operation mode" on the TOP screen.
⑨
Drain pump test run
Drain pump test run
Back
Run
Stop
Select the item.
③
Installation date
Installation date
yy
mm
dd
Back
Set
Set the date.
①
Installation settings menu #1
Installation settings
Installation date
Company information
Test run
Static pressure adjustment
Change auto-address
Next
Back
Select the item.
4
3
7
10
11
②
Installation settings menu #2
Installation settings
Address setting of main IU
IU back-up function
Infrared sensor setting
Previous
Back
Select the item.
14
13
17
Enter the phone number of
the company using up to 13
characters and then tap the
Set button.
⑥
Enter the Phone No.
Phone No.
Back
Set
Delete
Input the phone No & tap [Set].
Enter the company information.
④
Company information
5
6
Company information
Company
Phone No.
Back
Select the item.
Enter the company name
using up to 26 one-byte
characters and then tap the
Set button.
You can
enter alphanumeric, Japanese
Kana, Kanji, Cyrillic, or Chinese
characters.
⑤
Enter the Company
Company
Back
Set
漢字
Number
Alphabet
カナ
Next
Delete
Input the name & tap [Set].
汉字
TOP screen Menu
⇒
Service setting
⇒
Installation settings
⇒
Service password
The selected screen is
displayed.
⑦
Test run
Test run
Cooling test run
Drain pump test run
Compressor Hz fixed operation
Back
Select the item.
8
9
In case of Multi series (KX) models, the IU addresses registered
with the auto-address setting method can be changed with this
function.
This function changes the OU address for each IU. Select an IU
and,
Ⅰ
When an indoor unit is selected and the Change button
is tapped, the display changes to the Change auto-address
screen
⑫
.
Ⅱ
Tap the Set button to return to the screen
⑪
and display
the new address.
Ⅲ
Tap the Finish button to register the new address.
⑪
Change auto-address
Change auto-address
Back
Finish
IU address
OU address
Next
Change
Select the IU address to be changed.
Ⅰ
Ⅲ
⑫
Change auto-address
Change auto-address
Back
Set
IU address
No.2
OU address
No.0
Tap ▲▼ to set address & [Set].
Ⅱ
This is operable in case
of connecting duct type IU
equipped with the external static
pressure adjustment function.
Select the external static
pressure and tap the Set
button.
⑩
Static pressure adjustment
Static pressure adjustment
Back
Set
Tap ▲▼ to set the value of Pa.
AUTO
Pa