6-100
Safety
6Safety
[Caution] The emergency stop input(terminal block) on the user wiring in the controller can be used for safety
measures as shown in
Fig. 6-1
. Note that there are limits to the No. of switch contacts, capacity and
cable length, so refer to the following and install.
・ Switch contact...........................................Prepare a 2-contact type.
・ Switch contact capacity........................Use a contact that operates with a switch contact capacity of
approx. 1mA to 100mA/24V.
・ Cable length ................................................The length of the wire between the switch and terminal block
must be max. 15m or less.
・ Emergency stop output capacity.......Set it within 300 mA/24 VDC.
Connecting an external device outside of the above range will
cause a controller failure.