25
J Check of power supply
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If light up, OK.
If flash, refer to
"10-3. HOW TO
PROCEED "SELF-DIAGNOSIS"".
Does the POWER lamp on remote
controller light up?
Does LED on the inverter P.C. board
light up or flash? (Refer to "10-6.TEST
POINT DIAGRAM AND VOLTAGE.")
No
Replace the inverter
P.C. board.
Is there bus-bar voltage 260-325 VDC
between DB61 (+) and DB61 (–) on
the inverter P.C. board? (Refer to "10-
6.TEST POINT DIAGRAM AND VOLTAGE.")
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector (CN61)
between compressor and intelligent
power module.
Turn ON power supply and press
the TEST button twice.
Inverter P.C. board
(Solder side)
DB61
260-325 VDC
OCH467C