background image

Ax34601a_e_A5.doc / Feb-06 

 

Page 15 / 20 

5.2.5.

 

Parameters for generation of a linearisation curve 

Parameters described under this section will not appear in the menu when the linearisation has 

been switched off by setting „Linearisation Mode“ to „no“. 

 

„Linearisation Mode“ has to be set to either „1-quA“ or „4-quA“ to enable the linearisation 
function. This will change the linear measuring results into a non-linear display and a 

corresponding analogue output. 

 

There are 16 interpolation points available, which can be freely arranged over the whole 
measuring range in any distance. Between two points the unit automatically will interpolate 
straight lines. For this reason it is advisable to set many points into areas with strong bending, 

and to use only a few points in areas with little bending. 

 

Parameters P01_x to P16_x select 16 x- coordinates, representing the display values which the 
unit would normally show in the display. 

 

With parameters P01_y to P16_y you can specify now, which values you would like to display 
instead of the corresponding _x values. 

 

This means e.g. that the unit will replace the previous P02_x value by the new P02_y value. 

 

 

x- registers have to use continuously increasing values, e.g. the lowest display value 
must be set to register P01_x, and the highest display value must be set to P16_x 

 

Independent of the selected linearisation mode, the possible setting range of all 

registers  P01_x, P01_y,…, P16_x, P16_y is always  -99999 … 99999. 

 

1.

 

Linearisation-Mode = no  
All linearisation is switched off and the linearisation parameters do not appear in the menu 

 

2.

 

Linearisation-Mode = 1_quA 

Linearisation is defined for positive values only, e.g. for display values 0, …, 99999.  
Negative display values will appear as a mirror of the positive settings. 
To avoid discontinuity it is advisable to set the (P01_x, P01_y) coordinates to the zero point of the 

measuring range. Negative settings are allowed for y-coordinates only, but not for x-coordinates. 

 

3.

 

Linearisation-Mode = 4_quA 
Linearisation is defined over the full numeric range (i.e. -99999, …, 99999)  

 

4.

 

For measuring values outside of the defined linearisation range, please note: 
If the measuring value is lower than P01_x, the linearisation result will always be P01_y. 

If the measuring value is higher than P16_x, the linearisation result will always be P16_y.

 

 

Summary of Contents for AX346

Page 1: ...oder 0 4 20 mA with individual scaling Operation modes to display input A input B or combined values A B A B AxB and A B Selectable linearisation function with 16 interpolation points Adjustable analo...

Page 2: ...s a must to observe all general and also all country specific and application specific safety standards When this unit is used with applications where failure or maloperation could cause damage to a m...

Page 3: ...ic Set Up and Operational Parameters 10 5 1 Basic Set Up 10 5 2 Operational Parameters 11 5 2 1 Operational parameters with single channel mode 11 5 2 2 Operational parameters with dual channel mode 1...

Page 4: ...of the possibilities to calculate combined values like difference or ratio of the two inputs and by the in built facility of programmable linearisation this unit is also suitable to operate as a signa...

Page 5: ...provide DC supply from a 17 to 30 volts DC power unit The current consumption depends on the level of the input voltage and is typically 130 mA with 17 volts and 80 mA with 30 volts sensor current tak...

Page 6: ...nputs 2 4 Adjustable Analogue Output The unit provides a voltage output with ranges 0 10 volts or 10 to 10 volts output current max 2 mA and a current output 0 4 20 mA external load 0 300 Ohms The res...

Page 7: ...20 mA there is no need to change any jumper settings and you may skip this section Where however one or both inputs should be used for voltage it is necessary to set the jumpers as shown below To acce...

Page 8: ...oltage range you can modify the corresponding input to accept voltages up to 120 volts by adding a serial resistor to the input terminal please observe safety standards The subsequent formula shows ho...

Page 9: ...e next digit will be highlighted blink This procedure allows to set all digits to the desired values After the most significant digit has been set the low order digit will blink again and you can do c...

Page 10: ...nput A and input B separately A u B Summing mode input A input B A B Differential mode input A input B A d B Ratio mode input A input B A m B Multiply mode input A x input B Bright Brightness of displ...

Page 11: ...every menu and are absolutely identical with all modes Therefore these parameters are described only once and separately under section 5 2 4 To exit the parameter menu you can either press the ENTER...

Page 12: ...tely A LED bar in the most significant decade of the display indicates if your actual reading is channel A or channel B Menu Selection Text Description Input A Input range channel A in U Voltage input...

Page 13: ...isplay Choose from the formats shown in the display 5 2 3 Operational parameters for the combined modes A B A B AxB A B This mode provides the possibility to display the single channel results A or B...

Page 14: ...he analogue output depends only from the value shown in the display of the unit and from the scaling parameters shown below Therefore the analogue signal would also contain possible combinations and c...

Page 15: ...s This means e g that the unit will replace the previous P02_x value by the new P02_y value x registers have to use continuously increasing values e g the lowest display value must be set to register...

Page 16: ...following picture explains the difference between the linearisation modes 1_quA und 4_quA x y P1 x 0 P1 y 0 Linearisation Mode 1_quA x y Linearisation Mode 4_quA P1 x 1000 P1 y 900 P8 x 0 P8 y 750 P1...

Page 17: ...ingle mode Dual mode Combined modes Linearisation modE inPutA inPutA inPutA briGht StArtA StArtA StArtA UPdAt End A End A End A CodE dPoi A dPoi A dPoi A LinEAr FiLt A FiLt A FiLt A A CHAr inPutb inPu...

Page 18: ...Ax34601a_e_A5 doc Feb 06 Page 18 20 6 2 Dimensions 96 0 110 0 44 0 10 0 8 0 91 0 1 2 3 4 10 9 1 2 3 4 5 6 7 8 48 0 9 0 21 0 129 0 140 5 Panel cut out 91 x 44 mm...

Page 19: ...ltage Ri 30 kOhms Resolution 14 bits 13 bit sign Accuracy 0 1 1 digit Analogue outputs 0 4 20mA max 300 Ohms 0 10V max 2 mA Ambient temperature 0 45 operation 25 70 storage Housing Norly UL94 V 0 Disp...

Page 20: ...Filter A 0 4 1 1 09 Input Mode B 0 2 1 1 11 Start value B 99999 99999 0 5 12 End value B 99999 99999 1000 5 13 Decimal point B 0 5 0 1 15 Average filter B 0 4 0 1 14 Proportional Factor 10000 10000 1...

Reviews: