Ax34601a_e_A5.doc / Feb-06
Page 19 / 20
6.3.
Technical Specifications
AC power supply
:
115/230 V (+/- 12,5 %), 7,5 VA
DC power supply
:
24V (17 – 30V), approx. 100 mA (without sensor)
Aux. output for sensor
:
24V DC, +/- 15%, 100mA (with AC and DC power)
Inputs :
2 analogue inputs (+/-10V, 0..20mA, 4..20mA)
Input impedance
:
Current: Ri = 100 Ohms, voltage: Ri = 30 kOhms
Resolution :
14 bits (13 bit + sign)
Accuracy :
+/- 0.1%, +/- 1 digit
Analogue outputs
:
0/4...20mA (max.300 Ohms)
0…+/- 10V (max. 2 mA)
Ambient temperature
:
0° - 45° (operation), -25° - +70° (storage)
Housing :
Norly UL94 – V-0
Display :
6 digit, LED, high- efficiency red, 15mm size
Protection class
:
IP65 on the front side, IP20 on the back
Terminal strips
:
Signals max. 1.5 mm²,
AC supply max. 2.5 mm²
Conformity and standards:
EMC 89/336/EEC:
EN 61000-6-2
EN
61000-6-3
LV73/23/EEC: EN 61010-1
Sampling time
:
25 msec (alternating channels 1 and 2)