6.5.17 Alarm relay
DTS 4132.timeserver Moser-Baer AG
====================================
ALARM CONFIGURATION 2
1 Alarmmask for relay
98 Return and save
99 Return and discard changes
Enter desired menu number>
Path: 2 Configuration
3 Alarms
1 Alarm relay
1. Alarm mask for relay (see chapter "6.5.18 Alarm mask")
6.5.18 Alarm mask
DTS 4132.timeserver Moser-Baer AG
====================================
ALARMMASK Page 1
[ ]=error disabled, [*]=error enabled
[*] Bit00: DTS restart [*] Bit01: Error bit1
[*] Bit02: Supply voltage too low [*] Bit03: Failure supply 1
[*] Bit04: Failure supply 2 [*] Bit05: Error voltage 5V
[*] Bit06: Error voltage 2.5V [*] Bit07: Error voltage 1.25V
[*] Bit08: Wrong time zone DCF [*] Bit09: Error Time Zone TC
[*] Bit10: Error bit10 [*] Bit11: Alarm input
[*] Bit12: Line 1 current high [*] Bit13: Error time zone line 1
[*] Bit14: Line 2 current high [*] Bit15: Error time zone line 2
Enter alarmnumber to alter mask
Press ENTER for next part, 99 to leave>
Path: 2 Configuration
3 Alarms
1 Alarm relay
Alarm mask for relay
Display of all the DTS 4132 alarms (64) on 4 pages. Pages can be scrolled through
with ENTER.
An alarm on the current page can be switched on or off by entering an error number.
The page can be exited with 99. The modifications will be saved or restored one menu
level higher in “ALARM CONFIGURATION“. All Alarms with “error bitxx“ are not yet
used.
A description of individual errors can be found in appendix "C Alarm list".
The alarm masks for the various applications (E-mail, SNMP, SNMP Traps, alarm
relay) can differ.