Alarm list
Number Error message
Description / Action
Chap.
0
Reboot DTS
DTS 4132 restarted, no intervention required
1
Error bit1
Not used
2
Supply voltage too low
Power failure (internally measured)
support
3
Failure supply 1
Power failure 1 (only if redundant supply is on)
4
Failure supply 2
Power failure 2 (only if redundant supply is on)
5
Error voltage 5V
Power failure (internally measured)
support
6
Error voltage 2.5V
Power failure (internally measured)
support
7
Error voltage 1.25V
Power failure (internally measured)
support
8
Wrong time zone DCF
Check DCF configuration
9
Error Time Zone TC
Check TC configuration (DCF/Impulse)
6.5.3 / 5
10
Error bit10
Not used
11
Alarm input
Error from external device
12
Line 1 current high
Check MOBALine / Impulse line / DCF active line.
Alarm disappears only, if error is removed.
13
Error time zone line 1
Check time zone setting in (MOBALine / Impulse line / DCF
active line)
14
Line 2 current high
Check MOBALine / Impulse line / DCF active line.
Alarm disappears only, if error is removed.
15
Error time zone line 2
Check time zone setting in (MOBALine / Impulse line / DCF
active line)
16
Time source fail strat
Stratum too high: check time source
17
Failure time source TO
No time information from the selected time source within the
configured timeout: Check time source.
In slave mode: check link.
18
No valid time
20 min after starting no valid time
Check time source
19
NTP synch lost
Check NTP source
20
Error software trim
Quartz error or poor source quality
21
NTP failed
Check NTP configuration
22
NTP backup active
Check primary source
23
Syn. only diff too big
Check synchronization and source
24
No mail server
Check e-mail configuration, check connection
25
SNMP not running
Check SNMP and trap configuration
26
Error bit26
Not used
27
Error bit27
Not used
28
Error bit28
Not used
29
Error bit29
Not used
30
No DTS link (optical)
No connection via DTS link (optical link) in redundant
operation. Check connection.
31
No DTS link (LAN)
No connection via LAN link in redundant operation. Check
LAN connection.
32
Change slave->master
Switch over slave -> master has occurred. Optionally, check
the time source of current slave.