5.8 IDENTIFICATION TEXT
It is possible to add a standard identification text (NAME) to all messages sent out by the
Mobeye MS100E. The alarm messages are a combination of the name and the alarm
text. A user defined identification has a length of maximum 20 characters. The default
identification text is ‘Mobeye’.
5.9 ALARM TEXT
Custom alarm texts can be programmed. These texts have a maximum length of 20
characters.
The following texts are programmed as factory default:
Power failure
TEXT2: power failure
Power restored
TEXT3: power restored
Triggered input 1
TEXT4: alarm 1
Triggered input 2
TEXT5: alarm 2
Restored input 1
TEXT6: Input 1 restored
Restored input 2
TEXT7: Input 2 restored
5.10 INPUT TYPE
The input type defines the character of the inputs IN1 and IN2. This can be Normally
Open (NO) or Normally Closed (NC). If an input is set to NO, the alarm will be triggered
as soon as the terminals of the input are closed. If the input is set to NC, the alarm is
triggered if the connection between the input terminals is broken.
The default input type is set to NO.
5.11 INPUT DELAY TIME
The input delay time defines the time that the inputs are triggered before an alarm is
initiated. If the input returns to the non-alarm status within the delay time, no alarm is
sent. The delay time can be set between 0 and 999 seconds.
As default, the input delay time is set to 1 second.
5.12 INACTIVE TIME
The “inactive time” defines the time the movement sensor, input 1 or input 2 is not active
after an acti
vation. If the time is set to “0” (minutes), the input is active again immediately
after returning to the non-alarm status. If the time is set to e.g. 30 minutes, the input
remains inactive for the first 30 minutes. If the input is again (or still) activated after these
30 minutes, a new alarm message is sent. The inactive time can be set between 0 and
60 minutes.
As default, the inactive time is set to “5” for all inputs.
5.13 POWER FAILURE DELAY TIME
The power failure delay time defines the time that the power fails before an alarm is
initiated. If the power is restored within the delay time, no alarm is sent. The delay time
can be set between 0 and 60 minutes. As default, the delay time is set to 1. Take care
that a back-up battery needs to be placed in order to receive a power failure alarm
message.