V18.4
Art. No: MH-BA-25
Page 15
3.3.5.8 Reset counter
•
You can reset the operating hours of the individual heating elements. The
total operating time of the boiler cannot be reset.
•
Select the desired heating element or all heating elements with the arrow keys
(11 and 12) and confirm with the Enter key (13). Select YES or NO with the
arrow keys (11 and 12) and confirm with Enter.
3.3.6 Programs/log data menu
3.3.6.1 Preinstalled programs
MHRE + MHRQ1
Only with MHRQ1
Day Screed curing
Functional
heating
OE
standard
OE
standard
Suissetec Cement
Suissetec
DIN 1264-4
DIN 1264-4
B 3732
B 2242-2
Calcium
sulphate
CaSO
4
1
25°C
25°C
20°C
20°C
20°C
20°C
2
30°C
25°C
25°C
25°C
20°C
20°C
3
35°C
25°C
30°C
30°C
20°C
20°C
4
40°C
50°C
35°C
35°C
20°C
20°C
5
45°C
50°C
40°C
40°C
20°C
20°C
6
50°C
50°C
45°C
45°C
20°C
20°C
7
50°C
50°C
45°C
50°C
20°C
25°C
8
50°C
45°C
50°C
20°C
25°C
9
50°C
35°C
50°C
20°C
25°C
10
50°C
25°C
40°C
20°C
50°C
11
50°C
30°C
20°C
50°C
12
50°C
20°C
20°C
50°C
13
50°C
20°C
20°C
50°C
14
50°C
20°C
20°C
15
50°C
20°C
16
50°C
20°C
17
45°C
20°C
18
35°C
20°C
19
25°C
20°C
20
20°C
21
25°C
22
25°C