Troubleshooting guide (en) 07/2020 - v.1.1 ©Copyright 2019-2020: Mobile Industrial Robots A/S.
17
Error code
Error type
Description
Solution
1001, "SICK PLC
(MIR100/200):
Receiving SICK
Safety PLC data
timed out."
Hardware
error.
Can resolve
itself.
The communication
between the safety
PLC and the robot
computer is faulty.
Replace the Ethernet cable from the
safety PLC and the router with an
Ethernet cable you are certain is
functional (see
).
If the issue persists, swap the port the
Ethernet cable connects to in the
router. If a new error is shown,
replace the router. If the error
remains the same, try the same steps
but with the Ethernet cable that
connects the robot computer to the
router.
1004:
"Unsupported
SICK program
version"
Hardware
error.
Requires
interaction.
You have modified the
SICK program on the
safety PLC. If you are
experiencing errors in
the safety system, we
cannot troubleshoot
programs with custom
modifications.
Download a new standard
configuration file from the robot
interface and upload it to the safety
PLC. Refer to the how-to guide
How to
apply the default configuration of the
SICK safety system on MiR100/MiR200
found on the Distributor site.
1005: "Gear
ratio
configuration
mismatch! Sick
is configured
with: xxx and
Robot software
is configured
with: yyy"
Hardware
error.
Requires
interaction.
Either the safety PLC or
the robot computer is
using the wrong gear
ratio configuration.
Refer to the solution in error
If the robot does not drive correctly
after this, contact Technical Support
for assistance with correcting the gear
ratio.
5101, "Unable
to connect to
camera."
Hardware
error.
Can resolve
itself.
The robot computer is
not able to
communicate to one of
the 3D cameras.
See the solution in error
(OpenNI): Waiting for connection is
taking longer than expected!" on
page 14