Troubleshooting guide (en) 07/2020 - v.1.1 ©Copyright 2019-2020: Mobile Industrial Robots A/S.
33
Error code
Error type
Description
Solution
1002, "SICK
(MIR500/1000)
Safety system
error: xxx
Hardware
error.
Can resolve
itself.
See error
(MIR500/1000) Robot is
in Emergency stop: xxx
on the previous page
1003, "Invalid
SICK program"
Hardware
error.
Requires
interaction.
You have uploaded a
SICK program that the
safety PLC does not
recognize.
Download a new standard
configuration file from the robot
interface and upload it to the safety
PLC. Refer to the how-to guide
How
to upgrade the SICK safety system for
MiR500/MiR1000
found on the
Distributor site.
1004:
"Unsupported
SICK program
version"
Hardware
error.
Requires
interaction.
You have modified the
SICK program on the
safety PLC. If you are
experiencing errors in
the safety system, we
cannot troubleshoot
programs with custom
modifications.
Refer to the solution in error
1005: "Gear ratio
configuration
mismatch! Sick is
configured with:
xxx and Robot
software is
configured with:
yyy"
Hardware
error.
Requires
interaction.
Either the safety PLC or
the robot computer is
using the wrong gear
ratio configuration.
Refer to the solution in error
If the robot does not drive correctly
after this, refer to the article
Guide
to gear ratios on MiR robots
found
under
Articles
on the Distributor site.
2100, "Voltage
monitor:
HWRevision"
Hardware
error.
Can resolve
itself.
An error has been
detected in the power
board.
Replace the power board. Refer to
the how-to guide
How to replace the
power board on MiR500/MiR1000
.