INSTALLATION INSTRUCTIONS 

Carel pAD digital wall stat/humidity sensor 

commercial packaged ventilation system units 

model MPR

 

 

THIS MANUAL IS THE PROPERTY OF THE OWNER. 

PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.

 

 

Carel pAD Digital Wall Stat/Humidity Sensor 

 

 

 
 

IMPORTANT 

1.

 

Disconnect power supply before installing the 
accessory to prevent the unit from operating during 
installation. 

2.

 

The use of this manual is specifically intended for a 
qualified installation and service agency.  All installation 
and service of these kits must be performed by a 
qualified installation and service agency. 

3. 

These instructions must also be used in conjunction 
with the Installation and Service Manual originally 
shipped with the appliance, in addition to any other 
accompanying component supplier literature.

 

 
 

Application 

The Carel pAD (Ambient Display) wall thermostat/humidity 
sensor is used in conjunction with the Carel pCO3 controller 
mounted on model MPR Packaged Rooftop Commercial 
Ventilation units.   

 

Functions of the pAD include: 

 

Change temperature and humidity set points 

 

Clock display 

 

Alarm indication 

 

Time clock override 

 

Display of icons (refer to page 3) 

 

Specifications 

Power Supply Input: 

24 Vac (powered from unit)  

Power Consumption: 

1 Watt Maximum 

Operating Conditions: 

  32°F to 122°F 

  10 to 85% Relative Humidity 

(non-condensing) 

Index of Protection: 

IP30 (NEMA Type 1) 

 
 
 
 
 
 

 

Summary of Contents for MCP15-542.0

Page 1: ...qualified installation and service agency 3 These instructions must also be used in conjunction with the Installation and Service Manual originally shipped with the appliance in addition to any other accompanying component supplier literature Application The Carel pAD Ambient Display wall thermostat humidity sensor is used in conjunction with the Carel pCO3 controller mounted on model MPR Packaged...

Page 2: ... model MPR unit or on the pCO3 controller mounted on the model MPR unit using Table 2 1 to cross reference the correct connections Table 2 1 Terminal to Terminal Wiring Connection Terminal on pAD Terminal on Main Unit or pCO3 Controller G 24 Vac 503 on unit G0 ground 500 on unit Rx Tx positive pLAN Rx Tx on pCO3 J11 block Rx Tx negative pLAN Rx Tx on pCO3 J11 block 5 Holding the sensor on the oute...

Page 3: ... humidity setpoint press the Hum button and the Humidity setpoint will be displayed Use the Up or Down arrows to change the setpoint Unoccupied Mode Override to Occupied Mode In unoccupied mode you can press the Sleep button to activate Occupied Override Each press of the button increases the override time by an hour To cancel wait a few seconds then press the Sleep button once and the override wi...

Page 4: ... therefore reserves the right to change design and specifications without notice Commercial Products Group Modine Manufacturing Company 1500 DeKoven Avenue Racine Wisconsin USA 53403 2552 Phone 1 800 828 4328 HEAT www modinehvac com Modine Manufacturing Company 2011 MCP15 542 0 ...

Reviews: