Set Permanent Configuration (SET_PCD):
This call sets the following configuration data for the addressed AS-i slave:
• I/O configuration
• ID code
• Extended ID1 code
• Extended ID2 code
The configuration data are stored permanently on the EEPROM of the AS-i/
PROFIBUS Gateway and are used as the expected configuration by the AS-i master
in the protected mode. The configuration data are specified by the manufacturer of
the AS-i slave.
If the addressed AS-i slave does not support an extended ID code 1/2, the value F
hex
must be specified.
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).
This command can only be executed in the configuration mode.
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
Get Extended Permanent Configuration (GET_PCD):
This call reads the following configuration data (configured data) of an addressed AS-i
slave stored on the EEPROM of the AS-i master:
• I/O configuration
• ID code
• Extended ID1 code
• Extended ID2 code
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
25
16
2
T
circuit
3
–
B
slave address
4
xID2
xID1
5
ID
I0
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
25
16
2
T
result
Summary of Contents for CM4-505-GV1
Page 2: ......
Page 6: ...AS i PROFIBUS Gateway The Used Symbols issue date 22 6 2001 6 ...
Page 8: ...AS i PROFIBUS Gateway Safety issue date 22 6 2001 8 ...
Page 16: ...AS i PROFIBUS Gateway Connections Displays and Operating Keys issue date 22 6 2001 16 ...
Page 22: ...AS i PROFIBUS Gateway Operating the AS i PROFIBUS Gateway issue date 22 6 2001 22 ...
Page 62: ...AS i PROFIBUS Gateway PROFIBUS DP issue date 22 6 2001 62 ...
Page 68: ...AS i PROFIBUS Gateway Commissioning Tools and Accessories issue date 22 6 2001 68 ...
Page 77: ......