AS-i/PROFIBUS Gateway
PROFIBUS-DP
is
s
u
e
d
a
te
2
2
.6
.2
0
0
1
40
The configuration data are specified by the manufacturer of the AS-i slave.
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
Store Actual Configuration (STORE_CDI):
With this call, the (actual) configuration data (I/O configuration, ID code, extended ID1
code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves (LAS)
is adopted in the list of permanent AS-i slaves (LPS).
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).
This command can only be executed in the configuration mode.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
26
16
2
T
circuit
3
–
B
slave address
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
26
16
2
T
result
3
xID2
xID1
4
ID
I0
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
07
16
2
T
circuit
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
07
16
2
T
result
Summary of Contents for CM4-505-GV1
Page 2: ......
Page 6: ...AS i PROFIBUS Gateway The Used Symbols issue date 22 6 2001 6 ...
Page 8: ...AS i PROFIBUS Gateway Safety issue date 22 6 2001 8 ...
Page 16: ...AS i PROFIBUS Gateway Connections Displays and Operating Keys issue date 22 6 2001 16 ...
Page 22: ...AS i PROFIBUS Gateway Operating the AS i PROFIBUS Gateway issue date 22 6 2001 22 ...
Page 62: ...AS i PROFIBUS Gateway PROFIBUS DP issue date 22 6 2001 62 ...
Page 68: ...AS i PROFIBUS Gateway Commissioning Tools and Accessories issue date 22 6 2001 68 ...
Page 77: ......