Setting Parameters
01/02 AWB8230-1413GB
142
Other functions
Inhibit direction
Under PNU b035, you can specify whether clockwise or
anticlockwise motor operation is permitted.
Starting behaviour
With the two parameters PNU b036 and b082, you can specify the
voltage ramp and the frequency for starting the motor.
Voltage ramp
If the overcurrent trip is triggered at an increased starting
frequency, you can reduce the starting current and the torque with
PNU b036.
Starting frequency
Under PNU b082, you can set the frequency at which the motor is
to start.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b035
Inhibit
direction
–
–
00
Motor can run in both directions
00
01
Motor can only run clockwise
02
Motor can only run anticlockwise
Figure 149: Function chart for voltage ramp reduction
f
o
: Output frequency
U
2
: Output voltage
U
2
FWD
PNU b036 =
PNU b082
00
01
06
f
o
Figure 150: Function chart for starting frequency
f
o
: Output frequency
U
2
: Output voltage
U
2
FWD
PNU b036
PNU b082
f
o
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b036
Voltage ramp
to starting
frequency
–
j
00
Start without voltage reduction.
06
01
Minimum voltage reduction, approx. 6 ms
...
06
Maximum voltage reduction, approx. 36 ms
b082
Increased
starting
frequency
–
j
0.1 to 9.99 Hz
The motor starts with this frequency.
0.5