01/02 AWB8230-1413GB
Other functions
147
Initialization
Two different types of initialization are available:
• Clearing the fault history register
• Restoring the default parameter settings (default setting)
To delete the fault history register or to restore the factory default
settings, proceed as follows:
X
Make sure that PNU b085 holds the value 01.
X
Under PNU b084 (initialization), enter 00, 01 or 02.
X
Press the ENTER key to save the value.
X
On the keypad, press both arrow keys and the PRG key at the
same time and keep them pressed.
X
While holding the arrow and PRG keys, briefly press the OFF
key.
X
Now release all keys again. The display shows
d001
.
Initialization is now complete.
Country version
Here, you define the country-specific parameter set which will be
loaded during initialization (
a
PNU b084).
Frequency factor for display through PNU d
007
The product of the output frequency and this factor is displayed
under PNU d007.
OFF key disabled
Here, you can disable the OFF key located on the keypad or remote
operating unit.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b084
Initialization
–
–
00
Clearing the fault history register
00
01
Restoring the default parameter settings
02
Deleting the fault history register and restoring the default
settings
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b085
Country
version
–
–
00
Japan
01
01
Europe
02
USA
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b086
Frequency
factor
j
j
0.1 to 99.9
The product of the value displayed under PNU d001 and this
factor is displayed at PNU d007. This value is also available
at the FM terminal.
1.0
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b087
OFF key
disabled
–
j
00
OFF key always active
00
01
OFF key not active with control through the FWD/REV
terminals
efesotomasyon.com - Klockner Moeller - inverter