Appendix
01/02 AWB8230-1413GB
172
b024
Motor current limitation 2
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
–
1
138
b025
Tripping current 1 for motor current limitation
[A]
I
e
x
1.5
138
b026
Time constant 1 of motor current limitation
[s]
1.0
138
b031
Software dependent parameter protection
• 00: Through SFT input; all functions inhibited
• 01: Through SFT input; function F001 possible
• 02: Without SFT input; all functions inhibited
• 03: Without SFT input; function F001 possible
• 10: Extended parameters adjustable in RUN mode
–
01
139
b034
Running time or Mains On time signal
[h]
0
100
b035
Inhibit direction
00: Motor can run in both directions
01: Motor can only run clockwise
02: Motor can only run anticlockwise
–
00
142
b036
Voltage ramp to starting frequency
• 00: Start without voltage reduction.
• 01: Minimum voltage reduction, approx. 6 ms
• ...
• 06: Maximum voltage reduction, approx. 36 ms
–
06
142
b037
Display mode
• 00: All parameters
• 01: Relevant parameters
• 02: Parameters saved under PNU U001 to U012
–
00
144
b080
Gain factor, analog output AM
–
180
57
b081
Gain factor, analog output FM
–
60
58
b082
Increased starting frequency
(e.g. with high level of friction)
[Hz]
0.50
142
b083
Pulse frequency
[kHz]
5.0
146
b084
Initialization causes
• 00: Clearing the fault history register
• 01: Selection of default settings
• 02: Deleting the fault history register and restoring
the default settings
–
00
147
b085
Country version
• 00: Japan
• 01: Europe
• 02: USA
–
01
147
b086
Frequency factor for display through PNU d007
–
1.0
147
b087
OFF key
• 00: Always active
• 01: Not active with control through the
FWD/REV terminals
–
00
147
b088
Motor restart after removal of the FRS signal
• 00: With 0 Hz
• 01: With current motor speed
–
00
148
b090
Permissible relative percentage duty factor for built-in
braking transistor
[%]
0.00
148
b091
Type of motor stop when Off button is pressed
• 00: Braking/deceleration ramp
• 01: Free run stop (coasting)
–
00
149
PNU
Function
Units
WE
Page
Setpoint