5 – 15
5.3
Connection of main conductors
Main conductor - minimum cross section:
Cleaning the main conductor connection
Cleaning the copper bars
Bolt tight line-side bars
Bracing the main conductors
Frame size
Rated current
I
u
Cross section Cu bars
2)
bare/bare
black/bare
[A]
[mm2]
1)
[mm2]
1)
IZM(IN).1-...
630
1 × 40 × 10
1 × 40 × 10
800
1 × 50 × 10
1 × 60 × 10
1000
1 × 60 × 10
1 × 60 × 10
1250
2 × 40 × 10
2 × 40 × 10
1600
2 × 50 × 10
2 × 50 × 10
IZM(IN).2-...
800
1 × 50 × 10
1 × 50 × 10
1000
1 × 60 × 10
1 × 60 × 10
1250
2 × 40 × 10
2 × 40 × 10
1600
2 × 50 × 10
2 × 50 × 10
2000
3 × 50 × 10
3 × 50 × 10
2500
2 × 100 × 10
2 × 100 × 10
3200
3 × 100 × 10
3 × 100 × 10
IZM(IN).3-...
4000
4 × 100 × 10
4 × 100 × 10
5000
5 × 100 × 10
5 × 120 × 10
6300
6 × 120 × 10
6 × 120 × 10
1) Other Cu bar sizes possible, but the total Cu cross section must not be less.
2) Aluminium bars - please enquire.
ATTENTION
On 4-pole circuit-breakers, the neutral conductor must
always be connected all on the left (front view).
Otherwise this can cause malfunctions of the electronic
overcurrent release.
Connection of cables directly on the circuit-breaker
connections is not permissible.
Circuit-breaker
Steel-wire brush
Metal cuttings
Remove