Incoming circuit-breaker RA-DI
01/08 AWB2190-1430GB
38
Functions overview RA-DI
Engineering
Basic functions RA-DI
a
Page
Power incomer
Knockout plate for cable entry with M20 and M25 cable glands
Unit power supply via round cable up to 6 mm
2
Busbar supply with 7
x
2.5/4 mm
2
round cable
Line protection
Line overload and short-circuit protection to IEC/EN 60947-2 and DIN VDE 0100 part 430
Rated operational current: 16 to 25 A (factory default: 20 A)
Short-circuit protective
device for motor starter
Short-circuit protctive device for motor starter (groups) RA-MO to IEC/EN 60947-4-1, type “1”
coordination, short-circuit tripping current: 130 A to 210 A (factory default: 130 A)
Main and maintenance
switches
Power disconnecting device with lockable handle to IEC/EN 60947-1
Communication
AS-Interface
®
slave specification 2.1 for 31 stations
Display
Differentiated diagnostics LEDs: States, Power, Error
Signalling of switch position via AS-Interface
®
Figure 34: Example arrangement, Rapid Link system with RA-DI, RA-MO and RA-SP
e
M
3
h
1.5 mm
2
2.5 mm
2
/ 4 mm
2
3
AC 400 V
h
,
50/60 Hz
24 V
H
RA-DI
Q1
M
3
h
e
e
M
3
h
1.5 mm
2
1.5 mm
2
RA-MO
RA-SP
RA-MO
M
3
h
e
Motor Control Un
i
ts RA-MO,
Spee
d
Control Un
i
ts RA-SP
D
i
sconnect
Control Un
i
t RA-DI
F
6 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
RA-SP
1.5 mm
2
PES
PES
PES
PES
⎧ ⎨ ⎩
= 130 A to 210 A
F
20 A at 2.5 mm
2
F
25 A at 4 mm
2
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...