Motor starter RA-MO
(to Version 2.x)
01/08 AWB2190-1430GB
58
Quick stop
When the input signal arrives (rising edge), the motor starter
electronics de-energize the assigned contactor. The input signal
must be applied for at least 18.5 ms. As soon as the PLC output is
reset (falling edge), the contactor can be switched on again.
Whether the input signal is still applied during the reset or during
restarting of the PLC output as no effect
Sensors with break contacts can also be used. In this case the
motor starter’s DIP switch must be set accordingly.
LED signal on Quick stop:
LED FWD or REV is lit when the PLC has set the associated
direction of rotation bit. LED FWD or REV flashes when the
contactor has been switched off through the Quick stop and the
PLC’ direction of rotation bit continues to be set.
Figure 61: Quick stop in Automatic mode
(Example: I3 and forward rotation)
a
13.5 ms
g
5 ms
b
dependant upon PLC programme
I3
I3
O1
O1
(from PLC)
(from
PLC)
Signal
Signal
to DIL
to DIL
a
b a
a
b a
I3
I3
O1
O1
(from PLC)
(from
PLC)
Signal
Signal
to DIL
to DIL
a
b a
a
b
a