01/08 AWB2190-1430GB
Engineering
87
Selection criteria, RA-SP2…
Select a suitable RA-SP2-34…-… according to the rated motor
current. The RA-SP’s rated output current must be greater than or
equal to the motor’s rated current.
Table 19: Overview of technical data of RA-SP2:
Permissible setting ranges/
supply data
Factory setting
075
1K1
1)
2K2
075
1K1
2K2
Assigned motor shaft rating
At 400 V
0,37 ti
0,75 kW
0,75 to
1,1 kW
1,1 to
2,2 kW
0.75 kW
1.1 kW
2.2 kW
At 460 V
k
to 1 HP
m
to 1 HP
1 to 3 HP
1 HP
1 HP
3 HP
Apparent power at output
F
1,9 kVA
F
2,2 kVA
F
4,3 kVA
1.9 kVA
2.2 kVA
4.3 kVA
Mains supply voltage
3 AC 400 V
(342 V – 0 % to 506 V +0 %)
Supply frequency
50/60 Hz (47 Hz – 0 % to 63 Hz +0 %)
Mains input current
3, 3 A
3.6 A
2)
6.4 (7) A
4)
3.3 A
3, 5 A
7A
Rated operational current
I
e
(motor connection)
2, 5 A
2.8 A
3)
5 (5.5) A
5)
2, 5 A
2, 8 A
5A
Permissible overcurrent (b22)
* for a duration of 60 s (once every 10 min)
3.75 A*
(= 150 %)
4.2 A*
(= 110 %)
7.5 A*
(= 136 %)
3, 1 A
(= 125 %)
3.5 A
(= 92 %)
6, 25 A
(= 114 %)
Tripping current for electronic
motor protection (b12)
1.25 to
3 A
1,9 to
4,56 A
2.75 to
6.25 A
2, 5 A
3.53 A
5A
Heat dissipation at 5 kHz pulse frequency
F
44 W
F
50 W
F
92 W
44 W
50 W
92 W
Output frequency
1. Fixed frequency (A21)
0.5 to 50 Hz, max. 360 Hz
30 Hz
30 Hz
30 Hz
2. Fixed frequency (A22)
0.5 to 50 Hz, max. 360 Hz
40 Hz
40 Hz
40 Hz
3. Fixed frequency (A23)
0.5 to 50 Hz, max. 360 Hz
50 Hz
50 Hz
50 Hz
Analog fixed frequency through potentiometer
0.5 to 50 Hz, max. 360 Hz
approx. 10
Hz
approx. 10
Hz
approx. 10
Hz
Acceleration time (F02)
0.1 to 3000 s
10 s
10 s
10 s
Delay time (F03)
2 s
2 s
2 s
U
/
f
-characteristic (A44)
Linear, square-wave
linear
linear
linear
Pulse frequency (b83)
0.5 to
16 kHz
0.5 to 5 kHz
0.5 to
5 kHz
5 kHz
5 kHz
5 kHz
Max. permissible length of motor cable
(EMC, second environment, limit value class A)
15 m
15 m
10 m
15 m
15 m
10 m
1) The speed control unit RA-SP2…1K1… is based on the series DF5-340-1K5 frequency inverters and has the same enclosure as the RA-SP2…075.
The supply ratings are reduced due to the smaller heat sink.
2) At a motor current of 2.8 A the supply current is 3.6 A.
3) The power section’s rated operational current (DF5-340-1K5) is 3.8 A and results in a mains input current of 5 A. To prevent inadmissible heat
generation, the output current is limited to 2.8 A.
4) At a motor current of 5 A the supply current is 6.4 A.
5) The power section’s rated operational current (DF5-340-2K2) is 5.5 A and results in a mains input current of 7 A. To prevent inadmissible heat
generation, the output current is limited to 5 A.