LW005-MP
13 www.mokosmart.com
➢
Instantaneous frequency:
Convert to decimal, then then divide by 1000, the unit is HZ.
The 2
nd
part will be sent in Port 7:
➢
Timestamp:
Standard UTC time.
➢
Time zone:
It is a signed number, convert to decimal, then then divide by 2, and this is UTC
time zone;
➢
Instantaneous active power:
Convert to decimal, then then divide by 10, the unit is W.
➢
Instantaneous power factor:
Convert to decimal, the unit is %.
7.3 Energy Payload
Energy payload will be sent in Port 8.
➢
Timestamp:
Standard UTC time.
➢
Time zone:
It is a signed number, convert to decimal, then then divide by 2, and this is UTC
time zone;
➢
Total energy:
Convert to decimal, then divide by 3200, the unit is KW
·
H.
➢
Last hour's energy data:
Convert to decimal, then divide by 3200, the unit is KW·H. This is the
energy data of the last hour: for example, if the reported time is 14:23, the total ebergy data
of the hour from 13:00 to 14:00 will be reported.
7.4 Over-voltage Payload
Over-voltage payload will be sent in Port 9.
➢
Timestamp:
Standard UTC time.
➢
Time zone:
It is a signed number, convert to decimal, then then divide by 2, and this is UTC
time zone;
➢
Over-voltage state:
01 means over-voltage state.
➢
Currents instantaneous voltage:
Convert to decimal, then divide by 10, the unit is V.
➢
Over-voltage threshold:
Convert to decimal, then divide by 10, the unit is V.
7.5 Sag-voltage Payload
Byte 0~3
Byte 4
Byte 5~8
Byte 9
Timestamp
Time zone
Instantaneous active power
Power factor
Byte 0~3
Byte 4
Byte 5~8
Byte 9~10
Timestamp
Time zone
Total energy
Last hour's energy data
Byte 0~3
Byte 4
Byte 5
Byte 6~7
Byte 8~9
Timestamp
Time zone
Over-voltage state
Currents instantaneous
voltage
Over-voltage threshold