Section 8 - Maintenance
WARNING
Ensure that you have fully read “Section 3 - Safety” before performing
maintenance or repair procedures on the E-Drive controller.
Always isolate your controller at source before you open the unit to inspect
it or replace fuses.
8.1 Cleaning and Inspection
Inspect the fan filters at regular intervals according to your own environment.
The filters are removable and a light tapping action removes loose dirt and
dust. Failure to do this reduces the flow of cooling air and may incur more
expensive repairs if internal components subsequently overheat. If filters do
become clogged, they need to be replaced and these can be obtained from
Mold-Masters
quoting model type and year of manufacture.
Any excess dust that has entered into the cabinet may be removed with a
light brush and vacuum cleaner.
If the equipment is subject to vibration, we recommend you use an insulated
screwdriver to check that no terminals have become loose.
External cable-looms should be checked to see that there has been no
damage to the flexible conduit, plugs or sockets. If the flex has been
squashed, if there is visible damage, or if there are any exposed conductors,
then, for your own safety, it must be replaced.
8.2 Replacement Parts
Mold-Masters
does not expect that you will need to repair any controller parts
at board level other than fuses. In the unlikely event of any board failure then
we provide an excellent repair and exchange facility for all our customers.
8.3 Change Fuses
There are two fuses in the 24V supply that are located inside the cabinet.
They are found to the lower rear area on the right side of the cabinet (when
viewed from the front).
8-1
MAINTENANCE
E-Drive Controller User Manual (with Pendant HMI)
© 2020 Mold-Masters (2007) Limited. All Rights Reserved.