5.5 Plate Settings Parameters
NOTE
Only a Supervisor (user level 12), or higher, may change these parameters.
Auto Mode Settings
Maximum Velocity - the maximum velocity the operator can enter in the
movement profile
Auto Ramp - The acceleration and deceleration rate used on every step
Torque Limit During Auto - The torque limit during all auto movements
Torque Warning at Stand Still - The torque warning threshold when the plates
are not in motion
NOTE
This is a warning message only. The E-Drive will not stop operating.
Torque Alarm During Move - The torque alarm threshold during any
movement
NOTE
This is an alarm situation. The E-Drive will drop out of Auto then disable the
servo motor. Use the Torque Monitor to help you find the proper setting for
this alarm.
Auto Idle Timeout - The controller will be moved out of auto if no trigger is
received for this amount of time. To disable this option, set the timer to 0 min.
Use Mid Opening Step - Select this option to use a mid opening step
Use Mid Closing Step - Select this option to use a mid closing step
5-8
E-Drive Controller User Manual (with Pendant HMI)
SETUP