9
INSTALLATION HEIGHT
STORM COLLAR
(INCLUDED WITH CAP)
(612 OR 1212)
FLASHING
SF FIRESTOP SPACER
(1 3/4" AIR SPACE
CLEARENCE TO
COMBUSTIBLES)
2" MIN. CLEARENCE
TO COMBUSTIBLES
14 1/2" SQUARE
OPENING IN JOIST
FLASHING
(612 OR 1212)
SEE TABLE 1 FOR
ROOF OPENING
SIZE
SC CHIMNEY CAP
SINGLE STORY INSTALLATION WITH ATTIC SPACE
FLUE OUTLET HEIGHT
POOR LOCATION
16 FT.
SEE TABLE
1 FOR ROOF
SF FIRESTOP
MIN.
SPACER
SF FIRESTOP
SPACER
SF FIRESTOP
SPACER
OPENING SIZE
SC CHIMNEY CAP
14 1/2" SQUARE HOLE
IN JOIST (1 3/4" AIR
SPACE CLEARANCE
TO COMBUSTIBLES)
86 FT. MAX.
14 1/2" SQUARE HOLE
IN JOIST (1 3/4" AIR
SPACE CLEARANCE
TO COMBUSTIBLES)
MULTIPLE STORY INSTALLATION
ATTIC SPACE
ATTIC SPACE
3 FT. MIN. HEIGHT,
AND 2 FT. MIN. ABOVE
ANY POINT WITHIN 10
FEET OF CHIMNEY.
2" MIN. CLEARANCE
TO COMBUSTIBLES
(TYPICAL ALL AROUND.)
3 FT. MIN. HEIGHT,
AND 2 FT. MIN. ABOVE
ANY POINT WITHIN 10
FEET OF CHIMNEY.
STORM COLLAR
(INCLUDED WITH CAP)
: SCS CHIMNEY SUPPORT REQUIRED EVERY 30 FEET OF INSTALLATION HEIGHT.
*
*
PREFERRED LOCATION
FIRST FLOOR AREA
FLUE OUTLET HEIGHT
SECOND FLOOR AREA
THIRD FLOOR AREA
I
NSTALLATION
P
REPARATION
F
IGURE
8
F
IGURE
9
F
IGURE
7
NOTICE:
Chimney must be correct height above the roof
or other obstruction for safety and for proper draft
operation. The chimney must be at least 3 feet
higher than the highest point where it passes
through the roof and at least 2 feet higher than
the highest part of the roof or structure that is
within 10 feet of the chimney, measured
horizontally. See Figures 7, 9, and 14.
53D9033. Rev 1 03/03