HBDV7 Series Direct Vent Gas Fireplace
8
54D8000
CleARANCeS
CleARANCeS to CoMBuStIBleS
W
ARNING
Follow these instructions carefully to ensure safe installation. Failure
to follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
71”
Minimum
12”
Minimum
12”
Max.
Min. 4”
From Either
Side Wall
FP2580
mantel clearances
Figure 4 -
Clearances
Ceiling
Combustible Mantel
12”
12”
FP2581
mantel clearances
Wall
Stud
Standoff
FP581
Top of Exhaust
Louvers
Side View
1"
2
56O
”
3"
4"
1
56O
”
2
56O
”
45°
FP2582
mantel side clearance
Wall
Combustible
Material Area
Side of Fire-
place Opening
FP58
top View
Figure 5 -
Mantel Clearances
MANtel CleARANCeS
Note:
The combustible area above the facing must not protrude
more than 3/4" from the facing. If it does, it is considered a mantel
and must meet the mantel requirements listed in this manual.
W
ARNING
Never obstruct or modify the air inlet or
outlet grilles (louvers). this may create a
fire hazard.
FP580
Note:
All mantel shelves, regard-
less of depth, should be a mini-
mum of 1” from top of fireplace.
Mantel shelf shall not exceed 1”
maximum depth at 1” minimum
height from opening.
Insulation
Board